Control and regulating system for free chlorine, pH and Redox, made of eSelect-M3 controller, block valves, connection for tube 10x14
mm, water filter with washable net cartridge 150 microns, methacrylate probe holder with proximity switch and adjustment flow system,
manual sampling, free inorganic and organic chlorine probe, (0 – 20) ppm measuring range, probe shows low pH dependence (pH
working range 4-12pH), chlorine measuring is not affected by isocyanuric acid, surfactants/flocculants presence, the probe is automatic
temperature-compensated, 0,7 mt probe cable, pH electrode with plastic body with cable 1 mt (Tmax=60° C Pmax=6 bar) working range
0÷14 pH, Redox electrode with plastic body with cable 0,5 mt (Tmax=60° C Pmax=6 bar) working range ± 1.000 mV, 4 buffer solution
55ml bottles (pH 4, 7, 9 and Redox 650 mV), 2 manual pumps wiring connection available in the central box trunking. The unit required
a constant flow rate between 30 and 40l/h, do not exceed the maximum operating pressure of 1 bar (free discharge at probe holder outlet)
while water temperature cannot overcome 45°C. The probe has integrated temperature compensation. Suitable for software EtaCloud
connection; optional accessory: connectivity kit.
Panel dimensions 400 x 600 x 0.80 mm